Extreme: Typical: Surfaces: Infiltration calculation using LifeBreath HRVs: Total load: 33497 + 8243 = 41,740 (muni worksheet shows 77,279)

41740 X 1.33 = 55,155 minimum heating plant size required


THIS FIGURE ASSUMES FULL GARAGE TEMP (+70) AND FULL GARAGE VENTILATION (.35) AND IS CONSERVATIVE IN THE HRV EFFECTIVENESS ASSUMPTION (.6)


Weil-McLain CGS-3 Boiler Rating: 57,000 (DOE Heating Capacity)

Fireplace Maximum Input Rating: 42,000 (steady state efficiency up to 87%)


Total load by space:

volumes: basement=6656(.1834) ground=7488(.2063) upper=8320(.2292) garage=13832(.3811)

Basement: 4292 + 1511 = 5803
Ground: 7373 + 1700 = 9073
Upper: 8548 + 1889 = 10438
Garage: 13284 + 3141 = 16426